15.04.490 Section E3902.2 Amended – Garage and Accessory Building Receptacles.
Section E3902.2 of the International Residential Code for One- and Two-Family Dwellings is hereby amended and shall read as follows:
E3902.2 Garage and accessory building receptacles. 125-volt, single-phase, 15- or 20-ampere receptacles installed in garages and grade-level portions of unfinished accessory buildings used for storage or work areas shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(2)]
Exceptions:
1. A dedicated ceiling mounted receptacle for a garage door opener.
2. A single receptacle supplied by a dedicated branch circuit that is located and identified for specific use by a cord- and plug-connected appliance such as a refrigerator or freezer.
3. A dedicated receptacle supplying a permanently installed fire alarm or security alarm system.
4. A dedicated receptacle supplying a sump pump.
(Ord. 19-28 § 39, 2019; Ord. 12-42 § 2, 2012.)