16.05.185 Table 315.7.6(1) Amended – Separation Distance between Wood Pallet Stacks and Buildings.
This section is included in your selections.
Table 315.7.6(1) of the International Fire Code is hereby amended to read as follows:
TABLE 315.7.6(1) SEPARATION DISTANCE BETWEEN WOOD PALLET STACKS AND BUILDINGS
WALL CONSTRUCTION
OPENING TYPE
WOOD PALLET SEPARATION DISTANCE (feet)
≤ 50 PALLETS
51-200 PALLETS
>200 PALLETS
Masonry
None
2
2
2
Masonry
Fire-rated glazing with open sprinklers
2
5
20
Masonry
Fire-rated glazing
10
15
20
Masonry
Plain glass with open sprinklers
10
15
20
Noncombustible
None
10
15
20
Wood with open sprinklers
---
10
15
20
Wood with open sprinklers
None
15
30
90
Any
Plain glass
15
30
90
(Ord. 19-37 § 17, 2019.)