16.05.285 Subsection 903.3.1.2.3 Amended – Attics.
Subsection 903.3.1.2.3 of the International Fire Code is hereby amended to read as follows:
903.3.1.2.3 Attics. Attic protection shall be provided as follows:
1. Attics that are used or intended for living purposes or storage shall be protected by an automatic sprinkler system.
2. Where fuel-fired equipment is installed in an unsprinklered attic, not fewer than one (1) quick-response intermediate temperature sprinkler shall be installed above the equipment.
3. Where located in a building of Type III, Type IV or Type V construction, attics shall comply with one of the following:
3.1. Provide automatic sprinkler system protection.
3.2. Construct the attic using noncombustible materials.
3.3. Construct the attic using fire-retardant-treated wood complying with Section 2303.2 of the International Building Code.
3.4. Fill the attic with noncombustible insulation.
(Ord. 19-37 § 36, 2019.)