Table D103.4 of the International Fire Code is hereby amended to read as follows:

TABLE D103.4 REQUIREMENTS FOR DEAD-END FIRE APPARATUS ACCESS ROADS

LENGTH
(ft)

WIDTH
(ft)

TURNAROUNDS REQUIRED IN ACCORDANCE WITH FIGURE D103.1

0-150

20

None Required

151-500

20

120-ft Hammerhead, or

60-ft "Y", or

78-ft diameter cul-de-sac without island, or

96-ft diameter cul-de-sac with island

501-750

26

120-ft Hammerhead, or

60-ft "Y", or

78-ft diameter cul-de-sac without island, or

96-ft diameter cul-de-sac with island

Over 750

Special approval required